BICSI Technician (TECH) Exam Study Guide (2026)

Everything the Technician (TECH) tests, topic by topic: what each section covers, the facts that come up most, and how to study it. Pair it with the free 15-question practice test.

The exam at a glance

Questions100 written questions (multiple choice, multiple response and enhanced matching, 3 to 5 options each), after a separate 12-task hands-on exam
Time2 hours for the written exam (no scheduled breaks; any break counts toward the time). Hands-on exam: 20 minutes per task
Passing scoreNot published. BICSI sets the written passing score by standard setting (Angoff method) and reports pass or fail, with a section-level report if you fail. Aim for 75% or higher in practice (our suggestion, not a BICSI figure)
FormatNo personal items or references in the test room; a calculator and a whiteboard are provided. The real written exam mixes multiple choice, multiple response and enhanced matching; this practice uses 4-option single-best-answer items. This prep covers only the written part, and the hands-on exam must be passed first
Certifying bodyBICSI
Test providerWritten exam: Pearson Professional Assessments (Pearson VUE) test centers. Hands-on exam: administered through BICSI, usually on the last day of TE350 Technician Training

Mind map: the whole exam on one screen

BICSI Technician (TECH)
Field Planning, Implementation and Design
Frequency to which Category 6A is specifiedPurpose of the onsite start-up surveyWhich ladder setup angle meets the usual ruleCore diameter of OM1 fiber
Pathways and Spaces
Maximum bends between pull points in a conduit sectionMinimum size of a TBB under TIA-607Bend radius for a 3-in. conduitMaximum spacing of J-hooks
Pulling Copper and Fiber Cable
Pulling tension limit for one 4-pair cableFiber cable part that takes the pulling loadLay used to store fiber cable at an intermediate pull pointPurpose of a swivel on a pulling grip
Terminating and Splicing
8 key facts
Testing Copper and Fiber
8 key facts
Troubleshooting Copper and Fiber
8 key facts
Retrofits, Integration and Convergence
8 key facts
Codes and Standards
7 key facts
Free with an account

Read the complete BICSI Technician (TECH) study notes for “Field Planning, Implementation and Design”

Our first full set of comprehensive notes, about 14 minutes of reading: Copper and fiber properties · Surveys, drawings and job plans · Materials and inventory · Safety, labeling and closeout, a worked exam example, the traps examiners use and a one-minute recap. Create a free account to read it and see how premium notes work before you decide.

Open the free dashboard

1. Field Planning, Implementation and Design

20% of the TECH written exam: copper and fiber properties, pre-construction and start-up site surveys, blueprints, job plans, materials inventory, site safety, labeling and job closeout.

Key facts

  • Copper categories: Category 5e is specified to 100 MHz, Category 6 to 250 MHz and Category 6A to 500 MHz.
  • Multimode core sizes: OM1 is 62.5/125 µm; OM2 to OM5 are 50/125 µm. Singlemode OS1a and OS2 use a core of about 9 µm.
  • A pre-construction survey confirms routes, access, spaces, obstructions and owner rules before the job plan is fixed; an onsite start-up survey confirms the site is ready.
  • The job plan sets tasks, crews, sequence, materials, tools, safety needs and coordination with other trades.
  • Estimate cable from the average run plus slack and allow for waste; count only whole pulls per box or reel.
  • Treat the site safety plan as binding: PPE, ladders, lifts, confined spaces, lockout/tagout and laser safety all come before schedule.
  • Label both ends of every cable and termination to the ANSI/TIA-606 scheme in the job documents.
  • Closeout includes as-built drawings, test records, labeling records, punch list clearance and warranty paperwork.

Flashcards

Frequency to which Category 6A is specified500 MHz.
Purpose of the onsite start-up surveyConfirm the site is ready and conditions still match the job plan before work starts.
Which ladder setup angle meets the usual ruleBase out 1 ft for every 4 ft of working height (4:1).
Core diameter of OM1 fiber62.5 µm.

Exam tip: Most planning items are small arithmetic or sequence questions. Convert the drawing scale first, then ask what must be true before anyone starts work.

2. Pathways and Spaces

20% of the TECH written exam: telecommunications spaces, bonding infrastructure, cable supports, outlets, sleeves and cores, poke-throughs, trays, raceways, inner duct and firestop.

Key facts

  • Conduit runs: no more than 30 m (100 ft) and two 90-degree bends between pull points.
  • Conduit bend radius: 6 times internal diameter up to 53 trade size (2 in.), and 10 times above it.
  • Fill guideline for three or more cables in conduit is 40%.
  • Noncontinuous supports such as J-hooks are spaced no more than 1.5 m (5 ft) apart, with limited sag.
  • Keep at least 75 mm (3 in.) above ceiling tiles so cables and tiles stay clear of each other.
  • Busbars: clean to bright metal, apply antioxidant where required and use listed two-hole compression lugs.
  • Bond a metal conduit to any bonding conductor run through it at both ends.
  • Firestop must match a listed system for that barrier, opening, annular space and penetrant. Re-seal after every change.

Flashcards

Maximum bends between pull points in a conduit sectionTwo 90-degree bends (180 degrees total).
Minimum size of a TBB under TIA-6076 AWG, with larger sizes based on length.
Bend radius for a 3-in. conduit10 times the internal diameter.
Maximum spacing of J-hooks1.5 m (5 ft).

Exam tip: When a firestop or bonding question offers an extra material or a shortcut, ask whether the listing or standard allows it. If it doesn't, that's the wrong answer.

3. Pulling Copper and Fiber Cable

12% of the TECH written exam: pull setup, pull strings and ropes, horizontal pulls in conduit and open ceilings, riser and horizontal backbone pulls, fiber-specific pulls and air-blown fiber.

Key facts

  • Maximum pulling tension for one 4-pair cable is 110 N (25 lbf).
  • Minimum bend radius for 4-pair balanced cable is 4 times the cable outside diameter.
  • Fiber: attach the pull to the strength members (aramid yarn or a pulling eye), never to the fibers or jacket alone.
  • Use a swivel and a breakaway or tension monitor sized to the cable's rating.
  • Top-down riser pulls use gravity and a controlled brake; bottom-up pulls must lift the whole weight.
  • Use a figure-8 lay at intermediate points to avoid adding twist to fiber cable.
  • Lubricant must be compatible with the jacket and acceptable for the pathway.
  • Air-blown fiber is moved through microduct by compressed air, which limits tension on the fiber.

Flashcards

Pulling tension limit for one 4-pair cable110 N (25 lbf).
Fiber cable part that takes the pulling loadAramid yarn or other strength members.
Lay used to store fiber cable at an intermediate pull pointFigure-8.
Purpose of a swivel on a pulling gripLets the cable rotate so twist doesn't build up.

Exam tip: For any pull, name the limiting factor first: tension, bend radius or twist. The right method is the one that protects it.

Test yourself on these topics

Take the free 15-question BICSI Technician (TECH) test, then save your results to unlock your Readiness Score and the mistakes bank.

Start the free test

4. Terminating and Splicing

18% of the TECH written exam (terminating copper and fiber 12%, splicing 6%): pre-termination, connecting hardware, multi-pair and four-pair IDC, coaxial and modular plug terminations, fiber termination and fiber and copper splicing.

Key facts

  • Keep pair twists as close to the termination as possible; no more than 13 mm (0.5 in.) untwist on Category 5e and higher.
  • Strip only as much jacket as the connector needs, and don't nick the conductors.
6 more key facts, 8 key notes, 100 flashcards and 375 practice questions for this topic are in premium.

Flashcards

Maximum pair untwist on Category 5e and higher13 mm (0.5 in.).

Exam tip: Termination questions usually hide one bad habit, such as too much untwist or an uninspected end face. Find the habit, then pick the fix.

5. Testing Copper and Fiber

7% of the TECH written exam: copper cable testing, Tier 1 fiber certification with a light source and power meter, and Tier 2 testing with an OTDR.

Key facts

  • Copper field testers check wire map, length, delay, delay skew, insertion loss, NEXT, PSNEXT, ACRF, PSACRF and return loss.
  • A permanent link test leaves out patch cords; a channel test includes them.
6 more key facts, 7 key notes, 100 flashcards and 375 practice questions for this topic are in premium.

Flashcards

Test configuration that includes patch cordsChannel.

Exam tip: Decide what the test is measuring and what it leaves out. Most wrong answers apply a channel idea to a permanent link, or a Tier 1 idea to an OTDR.

6. Troubleshooting Copper and Fiber

7% of the TECH written exam: copper cable troubleshooting, basic fiber troubleshooting with a power meter or visual fault locator, and advanced OTDR troubleshooting.

Key facts

  • A split pair has correct pin continuity but high NEXT because the pairs are not twisted as designed.
  • Reversed pairs, crossed pairs, shorts and opens show up on the wire map.
6 more key facts, 7 key notes, 100 flashcards and 375 practice questions for this topic are in premium.

Flashcards

Field fault that passes pin continuity but fails NEXTA split pair.

Exam tip: Start with what the fault does to the signal, then match the tool: wire map for pins, NEXT for twist, OTDR for distance and event type.

7. Retrofits, Integration and Convergence

12% of the TECH written exam (retrofits 5%, integration and convergence 7%): retrofit surveys, active circuits, cutovers, abandoned cable, network topologies and components, security, wireless, DAS, PON and other building systems.

Key facts

  • Before work in an existing site, identify active circuits and keep records of what is in service.
  • A cutover needs a schedule, pretesting, a rollback plan and owner sign-off.
6 more key facts, 7 key notes, 100 flashcards and 375 practice questions for this topic are in premium.

Flashcards

Main item to have in place before a cutoverA rollback plan with owner sign-off.

Exam tip: With integration items, identify the system first, then ask what it requires of the cabling: power, reach, media or a separate listed pathway.

8. Codes and Standards

4% of the TECH written exam: adhering to local, state and federal fire and building codes and applicable standards.

Key facts

  • The authority having jurisdiction (AHJ) decides how codes apply on the site.
  • Codes are law where adopted; ANSI/TIA and BICSI standards describe recommended practice unless a code or contract makes them mandatory.
5 more key facts, 7 key notes, 100 flashcards and 375 practice questions for this topic are in premium.

Flashcards

Who has the final say on code interpretationThe authority having jurisdiction (AHJ).

Exam tip: If a choice follows a standard but breaks an adopted code, the code wins. If it breaks the listing, it's wrong even when it looks practical.

How to pass

  • Field planning and pathways are 20% each, 40% of the written exam together. Study outlets, sleeves, supports, bonding and firestop as hard as you study testing.
  • TECH is the one installation exam here that uses multiple response and enhanced matching items. Read each stem for how many answers it wants.
  • 100 questions in 2 hours is 72 seconds each. Calculate loss budgets and drawing scales on the whiteboard, then check the units before you answer.
  • You have one year from your first hands-on attempt to pass both parts, with a 30-day wait after each failed attempt and 90 days after a third, so book the written exam early.

Frequently asked questions

How long should I study for the BICSI Technician (TECH) exam?

Most working candidates need 4 to 8 weeks at 45 to 60 minutes a day. Book your exam once your Readiness Score has stayed at 80 or higher for about a week.

Can I take the BICSI Technician (TECH) exam online?

BICSI's v15 handbook describes the RCDD exam at Pearson VUE test centers, not remote proctoring. Format: no personal items or references in the test room; a calculator and a whiteboard are provided. the real written exam mixes multiple choice, multiple response and enhanced matching; this practice uses 4-option single-best-answer items. this prep covers only the written part, and the hands-on exam must be passed first. Check pearsonvue.com/bicsi for the options in your country.

What score do I need to pass the BICSI Technician (TECH) exam?

Not published. BICSI sets the written passing score by standard setting (Angoff method) and reports pass or fail, with a section-level report if you fail. Aim for 75% or higher in practice (our suggestion, not a BICSI figure). The exam has 100 written questions (multiple choice, multiple response and enhanced matching, 3 to 5 options each), after a separate 12-task hands-on exam and a time limit of 2 hours for the written exam (no scheduled breaks; any break counts toward the time). hands-on exam: 20 minutes per task.

What are the most tested topics?

The outline covers field planning, implementation and design, pathways and spaces, pulling copper and fiber cable, terminating and splicing, testing copper and fiber, troubleshooting copper and fiber, retrofits, integration and convergence, codes and standards. Use the free practice test to see which ones you need most.

The premium BICSI Technician (TECH) study path

Premium BICSI Technician (TECH) prep is studied one topic at a time. Each step starts with that topic's key notes and flashcard deck, then its own question sets of 25, so you master one topic before you move to the next. When every topic is strong, the 6 full mock exams show you're ready.

3,000practice questions, every answer explained
6full-length mock exams, 100 questions each, timed
800flashcards with spaced repetition, sorted by topic
60comprehensive key notes across 8 topics

Your step-by-step study path

  1. 1
    Field Planning, Implementation and Design8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Notes free with an account
  2. 2
    Pathways and Spaces8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  3. 3
    Pulling Copper and Fiber Cable8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  4. 4
    Terminating and Splicing8 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  5. 5
    Testing Copper and Fiber7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  6. 6
    Troubleshooting Copper and Fiber7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  7. 7
    Retrofits, Integration and Convergence7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  8. 8
    Codes and Standards7 key notes, 100 flashcards, then 375 practice questions in 15 sets of 25
    Premium
  9. Final step: 6 full mock exams100 questions each, timed like test day. Pass them, then book your exam.
    Premium

Get every note, flashcard and question

Most popular · cancel anytime

Premium Monthly

$147/month
per exam
About $4.83 a day · a fraction of a retest fee, for the credential that gets you on the bid list
  • The RCDD exam: full prep for the v15 blueprint
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: numbers and formulas sheet, standards atlas, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews monthly until you cancel. Cancel in two clicks from your account; you keep access until the end of the month you've paid for. No minimum term.

Best value · 3 months free

Premium Yearly

$1,323/year
per exam
Pay for 9 months, get 12. Save $441 against paying monthly.
  • The RCDD exam: full prep for the v15 blueprint
  • 3,000 practice questions + 6 full mock exams per exam
  • 800 flashcards + 60 key notes per exam, by topic, plus mind maps
  • Spaced repetition + mistakes bank
  • Readiness Score & detailed reports
  • Video lessons as they release
  • Content updates during your access
  • 5 bonuses: numbers and formulas sheet, standards atlas, study planner and more
  • Pass Guarantee: complete the prep, pass or 100% back

Renews once a year until you cancel. We email you before each renewal. Cancel any time from your account; you keep access until the end of the year you've paid for.

Pass Guarantee. Complete the full prep, sit your exam within 60 days, and if you don't pass we refund 100% of your subscription payments. See the requirements
Secure checkout by Stripe Card, Apple Pay, Google Pay Pass Guarantee

Summarized from BICSI's official candidate information and the rules cited, checked October 2026. Confirm current requirements with BICSI.

Start the free test